COMBILOG 1022Data LoggerHardware Manual Version 1.04

Página 2 - Issue: 22.01.2010

1 GENERAL PRELIMINARY REMARKS1.1 About this ManualThe manual contains all important information concerning the function, installation and initia

Página 3

11 COMMUNICATION11.1 Bus InterfaceThe bus interface of the data logger is an RS485 interface ac-cording to the specifications of the EIA-RS485 USA sta

Página 4

11.3 Data FormatThe data logger COMBILOG 1022 supports following data formats:For-matStart-bitData-bitParity- bitStop-bitCharacter lengthA

Página 5 - CHAPTER SURVEY

11.4 Output FormatThe data format can be user defined by means of configuration software COMBILOG.EXE. The data logger adjusts the data formats acco

Página 6 - TABLE OF CONTENTS

format length range of valuesinteger 2 byte (dec - 32768) ≤ i ≤ (dec +32767)Real 4 Byte (dec – 2129) ≤ x ≤ (dec + 2129)Table 11.4

Página 7

Following points have to be considered, referring to the above example: Decimals are not cut off, but are rounded off. In case of overflow with a tr

Página 8

11.5 Transmission SequenceThe data are transmitted from and to the data logger with fol-lowing sequence:ASCII-ProtocolSD.. ..ED SD .. .. .. .. .. ..

Página 9

protokol baudrate T1 min T1 max T2 min T2 max T3 minT3 maxadjustable no yes yes no no yesASCII2400 bit/s4800 bit/s9600 bit/s19200 bit/s38400 bit/s0 1

Página 10 - GENERAL PRELIMINARY REMARKS

11.6 ASCII protocol11.6.1 Telegram Format for the ASCII ProtocolFor the request-and response telegrams the ASCII-protocol distinguishes be

Página 11 - 1.3 Contact for Inquiries

SD: Start-Delimiter (length = 1 byte):The Start-Delimiter SD marks the beginning of a telegram. It assumes the following values in an ASCII-protocol:S

Página 12 - SYSTEM DESCRIPTION

FCS: Frame-Check-Sequence (length = 2 byte):The Frame-Check-Sequence FCS identifies the running digital sum of the telegram. This is the sum of the AS

Página 13 - 2.2 Range of Application

this manual, which only explains the general use of the data logger COMBILOG 1022.1.3 Contact for InquiriesIn case of inquiries concerning t

Página 14

11.6.2 Instruction Set in the ASCII-ProtocolCheck sumrequest telegram reply with orderlyperformancereply incase of er-rorread device identificationwit

Página 15 - 2.3 Features

Check sumrequest telegram reply with orderlyperformancereply incase of er-rorRepeat reading the events from pointer 2 with # aa f cc <cr> >

Página 16

pointer setting. If there is no further communication within 1 minute, password release is deleted.For passwords, only capital letters and numbers ar

Página 17 - 2.4 Configuration Software

device identification (v...v) length = 28 char<vendor name> ASCII ("Friedrichs") 10 char<model name> ASCII ("COMBILOG&quo

Página 18

If the bit Mn in the module status is set it indicates that an error has occurred in the data logger. Valid is:M1 = 1: EEPROM error M5 = 1: RTC errorM

Página 19 - INSTALLATION

Coding <type of calculation>:ASCII "0": normal calculation of average valueASCII "1": calculation of average value with wind

Página 20 - 3.3 Ambient Temperature

error code (e) length = 1 char<error code> ASCII 1 charCoding <error code>:ASCII "1" event memory emptyASCII "2" read-

Página 21 - Pin assignment:

11.7 PROFIBUS protocol11.7.1 Telegram Format for the Profibus ProtocolFor data transmission via PROFIBUS following telegram formats are re

Página 22 - 3.5 Connection

SD: Start-Delimiter (length = 1 byte):The Start-Delimiter SD identifies the beginning of a telegram. It can assume the following values in the PROFIBU

Página 23 - 3.6 Power Supply

DA: Destination-Address (length = 1 byte):The Destination-Address DA identifies the address of the com-munication partner to whom the data shall be tr

Página 24

2 SYSTEM DESCRIPTION2.1 System OverviewThe COMBILOG 1022 is a data logger with compact design, combined with integrated LC-display and me

Página 25 - 3.7 Bus Connection

ResDataUnit: Response-Data-Unit (length = 0 ... n byte):The Response-Data-Unit identifies a data field in the response telegram which contains the dat

Página 26 - 3.8 Sensor Connection

11.7.2 Instruction Set in the PROFIBUS-ProtocolLayer 2-adoption in PROFIBUS protocol:With PROFIBUS every bus user has so-called "service access p

Página 27 - 3.10 Module Jack

A DSAP - respectively SSAP-entry is identified by setting the highest bit in the address byte of Destination-Address (DA) or Source-Address (SA) res

Página 28

PROFIBUS - layer 2 commandsDSAP service data to the module (ReqDataUnit) data from the module (ResDataUnit)read device identification0 ident no data &

Página 29 - SIGNAL PROCESSING

PROFIBUS - DP commandsDSAP ser-vicedata to the module (Re-qDataUnit)data from the module (Res-DataUnit)read, write and tare / reset channels56 SRD [&l

Página 30 - 4.3 Power Switch

<ident> device identification length = 32 byte<length vendor name> binary (hex 0A) 1 byte<length controller type> binary (hex 08) 1

Página 31 - Correction

bit 1 = 1: EEPROM error bit 5 = 1: (RTC-Error)bit 2 = 1: FLASH error bit 6 = 1: (currently not occupied)bit 3 = 1: ADC error …bit 4 = 1: configuration

Página 32 - 4.5 Internal Processing

Coding <host input>:hex 00: host input is not possiblehex 01: host input is possible (tare/reset/dig.out/setpoint values)Coding <type

Página 33

<channel value Pn> binary 1, 2 or 4 byteReqDataUnit: [<tare/reset> [ <P1> [ ... [ <Pn>] ] ] ]ResDataUnit: <K1 > . .

Página 34 - 4.7 Signal Processing

11.8 MODBUS protocol11.8.1 Telegram Format for the MODBUS-RTU ProtocolThe request and response telegrams in the RTU-mode used by the sensor modules st

Página 35 - FUNCTIONAL DESCRIPTION

For applications like outdoor use there is a version with stain-less steel housing available, as well as various other accessor-ies.Configuring of the

Página 36 - 5.1 Analogue Input Channel

11.8.2 Instruction Set in MODBUS-RTU ProtocolWith the MODBUS-protocol the data are read and written via register accesses. The following register acce

Página 37 - 5.1.1 Voltage Measurement

BYTNUM ... number of data bytes (max. 64)D0 - Dn ... data bytes (max. 64)CRC ... check sumCRC polynomial: u15 + u13 + 1CRC start value:

Página 38 - Voltage Measurement

Preset Single RegisterDescription:By this command a single register can be written.Request TelegramADR FNR REGSTA REGNUM CRC6 MSB LSB MSB LSB MSB LSBR

Página 39 - 5.1.2 Current Measurement

DiagnosticDescription:By this command a diagnostic telegram will be sent to the data logger. If the telegram has been received in correct form the mod

Página 40 - Current Measurement

Preset Multiple RegisterDescription:By this command a large, continuous field of registers can be written.Request TelegramADR FNR REGSTA REGNUM BYT-NU

Página 41 - 5.1.3 Resistance Measurement

Register ContentsChannel values in integer formatRegister Type Contents Range0000 ro/rw Channel 1 integer value -32768 ... 327670001 ro/rw Chann

Página 42 - Resistance Measurement

Note: The possibility of a writing command on the registers 0000 to 005F depends on the configuration. With the following channel types a writing

Página 43

x ... “V“: Universal programy.yy : VersionStatus informationRegister Type Contents Length0500 ro Module status 2 Byte0501..0502 ro Channel stat

Página 44

Channel informationRegister Type Contents Length1000 ro Channel 1 Variable type 2 Byte1001 ro Channel 1 Measuring principle 2 Byte1002 r

Página 45

Coding <Channel type>:hex 0 Empty channel (EM)hex 2 Arithmetic channel (AR)hex 3 Digital output channel (DO)hex 4 Digital input channel (DI)

Página 46 - 5.2 Digital Input Channel

logger via the RS485 bus. In this case the COMBILOG is used as a bus master to read the measured values from the slave modules.All data can be transmi

Página 47 - Signal diagram:

Read data from external channelRegister Type Contents Range2000 ro Channel 1 real High Word 0 ... 655352001 ro Channel 1 real Low Word 0 ..

Página 48 - -> 0) is counted

11.9 Sample ProgramThe task is:The measured value in channel 2 shall be read from the sensor module with the address number 10. The value has been co

Página 49 - + 10V .. 30V

11.10 Autocall FunctionThe auto call function enables the data loggerCOMBILOG 1022 to send messages automatically via modem or as SM

Página 50 - -> 0) oc

Format of the status message:= Time ; N ; Location ; SN ; A ; KS ; MS= Start-DelimiterTime Date/Time (12 character, format YYMMDDHHmmSS); delimiterN M

Página 51 - 5.3.1 Digital Status Output

11.11 Modem ConnectionIn case of using a telephone or GSM modem with theCOMBILOG the modem must at first be initialized by means o

Página 52

12 WEBSERVER12.1 GeneralThe Web server can be used to configure and view settings of the COMBILOG 1022. To access the COMBILOG 1022 web server type

Página 53 - 5.4 Arithmetic Channel

12.5 Data LoggerThis page gives a short overview of the logger configuration. Settings like general sample rate (for all channels but the ana-logue

Página 54

tivated the data logger outputs an ASCII formatted string to the serial interface with every logging interval.12.10 Logger ConfigurationUsing this pag

Página 55

13 SPECIFICATIONS13.1 Power Supply Voltage range: +10 ... 30 VDC Power input: depending on scan rateapprox. 240 mW at measuring rate 60 s = 20.00 mA

Página 56 - Arithmetic Operators

13.4 Analogue Inputs (8 per Module)as voltage input: Types of measurement: single-ended, differential Ranges: ±10 V / ±5 V / ±2.5 V / ±1.25 V / ±625

Página 57

2.3 FeaturesFunction: Measurement inputs for all common types of sensors for I, U and R. Several different sensors can be connected simu

Página 58

 Accuracy: 0.05 %, (dependent on range) Resolution: 0.003 .. 0.03 %,(dependent on range) Linearity: 0.01 % Temperature drift: 25 ppm/K5 ppm/K with

Página 59 - 5.8 Threshold Values

 Baud rate ASCII: 2,400 / 4,800 / 9,600 / 19,200 bps 38,400 bps SD Card interfaceHardware Manual COMBILOG 1022151

Página 60 - 5.9 Error Handling

13.7 Operating Conditions Operating temp.: -40 to +85 °C* Storing temperature: -40 to +85 °C(different values for operation with memory cards) Mois

Página 61 - DISPLAY / MENU OPERATION

13.9 Shell Material: Aluminium and ABS Dimensions: w 187 x h 97 x d 73 mmw 7.36 x h 3.82 x d 2.87 inch Weight: approx. 720 g Protection class: IP

Página 62 - Main menu

Ordering code Type-no.data logger COMBILOG, with 6 digital and 8 ana-logue inputs, RS232, RS485, Ethernet and USB in-terfaces, with 7 MB intern

Página 63 - Configuration menu

14 SIMPLIFIED DRAWINGS14.1 Front ViewHardware Manual COMBILOG 1022155171,00 mm187,00 mm98,00 mm

Página 64

APPENDIXA. Pinout Arrangements for analog Sensors at the Data Loggermeasurement ofvoltage voltage current single-ended differential single-endedmeas

Página 65

B. Pinout Arrangements for digital Sensors at the Data Loggerdigital status outputU+I/Odigital status recording frequency measurementI/O0 VI/O0 Vfprog

Página 66 - LED Display

C. Pinout Arrangements for analog Sensors of Th. Friedrichs (Examples)Voltage measurement, Voltage measurement,single-ended: differential:AIN 1SOURCE

Página 67

Resistance measurement, 4-line:AIN 1SOURCEIn +In -AGNDPt100 1 2 3 4 2010, 2014, 2015, 2017, 2018, 2019,Pt100 1 2 3 4 2020, 2030, 210

Página 68

 LED-status indication for the ethernet interface LC-display (4 x 16 characters) and push-/turn knob for op-erationMeasured value processing: Linea

Página 69 - Network settings

D. Pinout Arrangements for digital Sensors of Th. Friedrichs (Examples))Status: Frequ

Página 70 - Channels settings

E. Configuration Table for the Data Loggeroptiontype ofaveraging fordata storageoffsetcorrectiontime baseconv. factordata memorysummingresetthreshold

Página 71

F. Accuracy / Resolution / Noise / Linearity / Temp-DriftOverview measuring rangesgain stepgain factorvoltage meas-urementcurrent meas-urementresist.

Página 72 - Setting of the date and time

Overview measuring accuracy type of measurements voltage single-end.current measur.voltage dif-ferentialallgain stepgain factoraccuracy(1)resolutionno

Página 73 - Change

Voltage measurement - single-endedrange accuracy(1)(3)Resolution / noise(1)linearity(2)temperat. drift(2)±10 V 1.0 mV±5 V 0.5 mV±2.5 V 0.3 mV 0.01 % 0

Página 74 - 6.3.1 Remove Card

Voltage measurement - differentialrange accuracy(1)(3)Resolution / noise(1)linearity(2)temperat. drift(2)±10 V 3.0 mV±5 V 1.5 mV±2.5 V 0.8 mV 0.03 % 0

Página 75 - DATA STORAGE

Current measurementrange accuracy(1)(3)Resolution / noise(1)linearity(2)temperat. drift(2)25 mA 12.5 µA12.5 mA 6.25 µA 0.003 %6.25 mA 3.13 µA 0.05 %3.

Página 76 - 7.3 Storage Medium

Resistance measurementrange accuracy(1)(3)Resolution / noise(1)linearity(2)temperat. drift(2)20 kΩ 10 Ω10 kΩ 5 Ω5 kΩ 2.5 Ω0.003 %2.5 kΩ 1.25 Ω0.05 %1.

Página 77 - 7.4 Internal Data Storage

G. Algorithms for special meteorological ParametersIndex of constantsSVP = Saturation vapor pressure in hPaVP = Actual vapor pressure in hPa with air

Página 78

Saturation vapor pressure( )SVP TT C eC TTC TT=+123**by MAGNUS (1)Actual Vapor Pressure VP( ) ( )VP SVP HT C SP TT HT= − −* *by SPRUNG (2)Rel. humidit

Página 79

Communication: Integrated RS 485, RS 232, USB and Ethernet communic-ation interface Autonomous function independent of subsequent systems Definitio

Página 80

Standard deviationsxxnn=−∑∑−²( )²1 Vector mean value of wind direction (VecD) and wind speed (VecV)The components of th

Página 81

WV u u= +1222WD′ = arctan uu21 with 0 90° ≤ ′ ≤ °WDAs u1 and u2 may also be relative and arctan is only defined for a range 0°...90°, the true d

Página 82 - MASTER FUNCTION

H. Description of Short Real FormatThe data type occupies 4 byte (32 bit, corresponding 8 hexa-decimal numbers) which are placed a

Página 83

I. Notes for installing Configuration Software COMBILOG.EXEThe COMBILOG 1022 can completely be configured by means of the COMBILOG.EXE progra

Página 84

In case a software update for the data logger is necessary, the configuration program provides a download function, that sends the new pro

Página 85 - INITIATION AND TEST

3 INSTALLATION3.1 Mounting / FixingThe data logger COMBILOG 1022 has a snap-on mounting for installation on standard profile rails 35 mm (1.4 inch) ac

Página 86

Issue: 22.01.2010Technical data are subject to change!Hardware Manual COMBILOG 10222

Página 87 - ● 38400 Bit/s

3.3 Ambient TemperatureThe admissible ambient temperature for the data loggerCOMBILOG 1022 is -45 °C to +85 °C. The admissible ambient t

Página 88 - 10.1 Bus Interface

Description of the parts:Number Description Number Description1 USB9Module jack connection2 Ethernet 10 LED ERR (red)3 Voltage supply 11 LED RUN (gree

Página 89 - 10.2 Bus Structure

3.5 Connection  Connection: plug-in screw terminals  Nominal cross section: 1.5 mm² (0.02 square inch)unifilar/fine-strand (AWG 16) Length of wire

Página 90

3.6 Power SupplyFigure 3.2 Connection of the distribution voltageVoltage range +10 ... +30 VDCPower input 0.1 W typical (up to 1.1W maximum, depe

Página 91 - 10.4 Bus Cable

Non-regulated DC voltage between +10 and +30 VDC is suffi-cient for the power supply of the data logger COMBILOG 1022. The input is protected against

Página 92 - 10.5 Bus Plug

3.7 Bus ConnectionIn general the data logger is connected to the bus by applying the signal leads A and B of the incoming bus cable and A' and B&

Página 93 - 10.6 Bus Termination

Figure 3.4 Connection of the data logger to the bus by a stub cable3.8 Sensor ConnectionThe analogue and digital signal inputs and outputs are wire

Página 94

Following devices can be connected directly to the digital out-puts: signal lamps, small relays, switching relays for larger loads, ac

Página 95 - 10.7 Shielding

Note: It is necessary to take care that the current at the Module Jack is not higher than permitted. Thus, the power supply preferab

Página 96 - 10.8 PC Bus Connection

4 SIGNAL PROCESSINGThe data logger COMBILOG 1022 has eight analogue inputs and six digital inputs/outputs. Several different sensor signals as well

Página 97 - 10.9 Potential Equalization

 Copyright 1995-2010, Theodor Friedrichs & CO (Germany).Copyrights: Operating instructions, manuals and software are subject of copyr

Página 98

As inputs the I/Os can be used for collecting feed-back signals, for measuring frequencies, as counters or for receiving special serial 8-bit-Graycode

Página 99

4.4 Internal Reference Voltage, Offset- and Drift CorrectionAn internal reference voltage serves to adjust the entire ana-logue signal proce

Página 100 - COMMUNICATION

4.5 Internal ProcessingNext to collecting the analogue input signals, the analogue mul-tiplexer at the input of the circuit collects the internal refe

Página 101 - 11.3 Data Format

failure or breaking of the sensing element or short-circuit can also be realised. The data logger can be activated - by means of appropriate configura

Página 102 - 11.4 Output Format

4.7 Signal ProcessingArithmetical averaging is carried out using several measuring values. The averaging interval, which is the same for all chan-nels

Página 103 - Transmission in ASCII-format:

5 FUNCTIONAL DESCRIPTIONThe data logger COMBILOG 1022 has a total of 32 logical channels for the collection, processing and output of vario

Página 104 - Hardware Manual COMBILOG 1022

5.1 Analogue Input ChannelThe Analogue Input Channel collects and processes the sig-nals of the most common types of sensors. A large number of standa

Página 105 - 11.5 Transmission Sequence

5.1.1 Voltage MeasurementTwo methods are available for voltage measurement: single-ended and differential measurement.With the single-ended type the

Página 106

Voltage MeasurementFigure 5.1 Voltage measurement - single-endedFigure 5.2 Voltage measurement - differentialHardware Manual COMBILOG 102238Sour

Página 107 - 11.6 ASCII protocol

5.1.2 Current MeasurementFor current measurement the current source is connected between an analogue input (In+) and analogue ground (A

Página 108

Hardware Manual COMBILOG 10224

Página 109

Current MeasurementFigure 5.3 Current measurement with internal shuntFigure 5.4 Current measurement with external shuntHardware Manual COMBILOG

Página 110

5.1.3 Resistance MeasurementResistance measurement is carried out by means of voltage measurement at a resistor, measuring the resulting

Página 111

Resistance MeasurementFigure 5.5 Resistance measurement in 2-wire techniqueFigure 5.6 Resistance measurement in 3-wire techniqueFigure 5.7 Re

Página 112

Temperature Measurement with ThermocoupleThermocouples consist of two “thermoelectric wires” made of different materials (e.g. platinum and plati

Página 113 - Byte: 9 10 11 12

If the temperature is measured by external cold junction com-pensation, a second thermocouple of the same type is re-quired, which i

Página 114

Temperature Measurement with ThermocoupleFigure 5.8 Temperature measurement with internal cold junction compensation by special terminal clamp ICJ

Página 115

5.2 Digital Input ChannelThe following functions can be realized by means of the Digital Input Channel: Digital status recording Frequency measureme

Página 116

5.2.1 Digital Status RecordingFor the acquisition of digital status information (on/off, closed/open, left/right, etc.) the signal fed t

Página 117 - 11.7 PROFIBUS protocol

5.2.2 Frequency MeasurementWith frequency measurements the data logger counts the pul-ses within a certain time interval at the digital input. The use

Página 118

Frequency MeasurementFigure 5.11 Frequency measurementI/O 1time baseTB TB TBcounting1 2 3 1 2 3 1 2 3 1measurand(TB = 5 sec)signal diagram:- high le

Página 119

CHAPTER SURVEYPage1 GENERAL PRELIMINARY REMARKS...102 SYSTEM DESCRIPTION...123 INSTALLATION...

Página 120

5.2.3 Progressive CounterWhen configuring a digital input as a progressive counter the data logger COMBILOG 1022 constantly monitors the digital i

Página 121

5.3 Digital Output Channel5.3.1 Digital Status OutputThe digital output channel supports: digital status output, host-controlled digital status outp

Página 122

The thresholds can be freely defined by the user. The user can also preset the logical signal level (see also the configuration software COMBILOG.EXE)

Página 123 - PROFIBUS - layer 2 commands

5.4 Arithmetic ChannelBy means of the arithmetic channel sensor channels and con-stants can be connected with each other via arithmetic opera-tions. T

Página 124 - PROFIBUS - DP commands

spez1(INTERFACE; TYPE; START; VAR; DEFAULT)• INTERFACE• 1: RS232• 2: RS485• TYPE• 1: constant length• 2: variable length• START: start position (start

Página 125

Note: The calculation time of an Arithmetic Channel is min 0.2 ms. The overall calculation time is the sum of the times of all operand

Página 126

Arithmetic Operatorsoperations abbreviation timeAddition + 0.26 msSubtraction - 0.26 msMultiplication * 0.26 msDivision / 0.26 msModulo % 0.24 msTrunc

Página 127

Free space in RAM RAMSpace 0,1 msApplication specific function 1 spec 11)Application specific function 2 spec 21)Application specific function 3 spec

Página 128

The results of the inverse functions are given in radians (2π = 360°). At the function arcsin the value + 2π will be assigned to the Arithmetic Channe

Página 129 - 11.8 MODBUS protocol

5.5 Setpoint ChannelThis channel features transmission of values via bus to the data logger COMBILOG 1022. The values are allocated to the

Página 130

TABLE OF CONTENTSPage1 GENERAL PRELIMINARY REMARKS...101.1 About this Manual...

Página 131

5.9 Error HandlingThe data logger COMBILOG 1022 can detect independently certain defects, which are result of a line break, short-circuit or co

Página 132

6 DISPLAY / MENU OPERATION6.1 Display and OperationThe data logger COMBILOG 1022 has a display with 4 lines of 16 characters each, in order

Página 133

Main menu Note: The number, designation and indication of the measured value of the channels depend on the configuration.Hardware Manual COMBILOG 102

Página 134

Configuration menuNote: If the push/turn selection knob is pressed at any point in the configuration menu for about 1 second you will return to the in

Página 135

Setting of the display backlightNote: The value of the display backlight can be set in steps from 0 % to 100 %. With low values the display will be

Página 136

Setting the scan rate and the averaging intervalConfiguration menuNote: The scan rate determines after which time interval the measured values of the

Página 137

Setting of the Automatic Switch Off and the LED DisplayConfiguration menuNote: With the automatic switch off function the data logger

Página 138

Setting of the Baud Rate and the AddressConfiguration menuNote: Possible values for the baud rate are 2400, 4800, 9600, 19200 and 38400 bps. Additiona

Página 139

Lock or unlock the press/rotary knob inputConfiguration menuNormally the changing of configuration parameters by the press/rotary knob i

Página 140

Network settingsIf the powersave feature for the ethernet interface is enabled no connection can be established using this interface.Due to the relati

Página 141 - 11.9 Sample Program

5 FUNCTIONAL DESCRIPTION...345.1 Analogue Input Channel...355.1.1 Vo

Página 142 - 11.10 Autocall Function

Channels settingsIn order to change the values the press/rotary knob must be pressed. Thereby a cursor will be set on the first character of the value

Página 143

Display and delete the data memoryMain menuThe display shows the number of stored datasets and the max-imum capacity of the data memory. The fourth li

Página 144 - 11.11 Modem Connection

Setting of the date and timeIn order to change the date and the time the press/rotary knob must be pressed when the time(1) respectively dat

Página 145 - WEBSERVER

6.3 SD-CardIf a SD-card is inserted into the card slot an additional menu item is displayed in the main menu. Choosing this menu item one can update t

Página 146 - 12.9 Serial Channel

6.3.1 Remove CardIf a SD-card is configured as logging destination the card has to be logged off of the system before removing it. Otherwise written d

Página 147 - 12.13 Logout

7 DATA STORAGE7.1 General Remarks to Data StorageThe COMBILOG 1022 is able to store the calculated mean val-ues. Data storage with the COMBILOG 1022

Página 148 - SPECIFICATIONS

Conditional data storageMeasured values are stored in the memory as long as a condi-tion defined by the configuration program is valid

Página 149 - ±6.25 mV

7.4 Internal Data StorageThe COMBILOG 1022 is delivered with 8 MByte flash memory. For data recording 7 MByte memory are available as circular memory

Página 150 - 13.6 Interfaces

Memory demand for one record:Number of bytes = 8 + 4 * number of measured valuesThe duration of data recording until the data memory is filled can be

Página 151 -  SD Card interface

7.5 External Data Storage with SD CardThe data will be stored in a file on the SD Card. The name of the file depends of store mode. Three different mo

Página 152 - 13.7 Operating Conditions

9 INITIATION AND TEST...849.1 Before Connecting the Device...849.

Página 153 - 13.10 Circuit

Theodor Friedrichs & Co. delivers pre-formatted memory cards, that can directly used for the COMBILOG.Structure of the data file:Ident Friedrichs

Página 154

Note: With the Configuration program a ”;” or a “TAB” (ASCII 09hex) can be selected as delimiter and a “:” or a “;” is select-able as decimal point.M

Página 155 - SIMPLIFIED DRAWINGS

8 MASTER FUNCTION8.1 Master FunctionThe two interfaces and the master function of theCOMBILOG 1022 allows a configuration of

Página 156 - APPENDIX

 Configure all slave modules with the same bus parameters as the master data logger (same protocol type, same baud rate and parity). All modules must

Página 157 -

Figure 8.1 Example Master Slave SystemHardware Manual COMBILOG 102284Host-RechnerRS232BusmasterAdresse 01SlaveAdresse 02SlaveAdresse 03Sensoren Sens

Página 158 - Th. Friedrichs (Examples)

9 INITIATION AND TEST9.1 Before Connecting the DeviceBefore connecting the supply voltage to the data loggerCOMBILOG 1022, once agai

Página 159

RUN(green LED)ERR(red LED)meaningoffThe supply voltage has been selected too low or the power supply cannot supply the required power.off

Página 160 - Th. Friedrichs (Examples))

10 STRUCTURE OF THE BUS TOPOLOGYThe coupling of the data logger COMBILOG 1022 to a commu-nication bus is performed via an integrated RS485 interface.

Página 161

 Line length:depends on the transmission speed, max. 1.2 km (0.75 miles) per bus segment, max. 4.8 km (3 miles) via a phys-ical bus string with 3 rep

Página 162

10.2 Bus StructureThe bus structure is a line structure where each bus segment will be blanked off with characteristic impedance on both ends. Branche

Página 163

11.11 Modem Connection...14312 WEBSERVER...

Página 164

: :: :...Figure 10.4 Line structure with branchesThe RS485 interface permits the simultaneous connection and operation of a maximum of 32 bus users pe

Página 165

Note: These specifications refer to bus cables with a conductor cross section of 0.22 mm² and a permissible signal attenuation of max. 6 dB referred t

Página 166

10.5 Bus PlugFor installing the bus cable and the bus interface, 9-channel D-sub miniature plugs and sockets are used. The pin assign-ment for the RS

Página 167

Only signal leads A and B (and Shield) are absolutely obligat-ory for a (shielded) connection. All others can be installed to-gether with these signal

Página 168 - 0 00066 1 0 00115. * . *

The bus termination can be carried out in various ways.It can either be carried out via external resistors and a separate power supply, independent of

Página 169 - VP SVP HT C SP TT HT

make absolutely sure that the jumper clips are installed as in-dicated, and that the bus leads or the bus termination are not short-circuited by mista

Página 170

Bus parties such as controls (PLCs), computers (PCs), repeat-ers and interface converters, a.s.o., mostly offer the possibility of applying the shield

Página 171

10.9 Potential EqualizationThe difference between the actual physical voltage potentials DGND of all connections with the bus must not exceed ±7 Volt.

Página 172

If no other specifications are made on delivery, the data logger has address 1 and baud rate 19,200 bps, no parity as default. The adjustment can be c

Página 173 - COMBILOG.EXE

Note: The address “127” is reserved for broadcast transmis-sion in the PROFIBUS-protocol (Level 2) and may only be as-signed for these cases.Adjustme